Specifications
Temperature Sensor:
Pt1000, 0.000385 DIN.
Output Temperature Ranges:
User selectable – any range between -30 to 250°F with a minimum span of 40°F.
Temperature Limits:
Ambient: -4 to 158°F (-20 to 70°C); Process: -30 to 250°F (-34.4 to 120°C).
Accuracy:
Transmitter: ±0.1% FS; Probe: ±0.3% FS.
Thermal Drift Effects:
±0.002%/°C max.
Response Time:
250 ms.
Wetted Materials:
316 SS.
Process Connection:
1/2″ male NPT or 1/2 male BSPT.
Conduit Connection:
1/2″ female NPT or M20.
Probe Length:
2″ to 18″ (depending on model).
Pressure Limits:
2000 psi (137.9 bar).
Power Requirements:
10 to 35 VDC.
Output Signal:
4 to 20 mA (two wire loop powered).
Optional Display:
2 lines X 8 character LCD.
Enclosure Rating:
Weatherproof NEMA 4X (IP66) and Explosion-proof. Listed with FM for Class I, Division 1, Groups B, C and D, and dust ignition-proof for Class II, Division 1, Groups E, F and G and Class III atmospheres.
ATEX Certified: CE 2813 (Ex) II 2 G Ex db IIC T6…T4, Gb CE (Ex) 2813 II 1 D Ex ta IIIC T111°C Da, T6 Process Temp =80°C, Temperature Class T5 Process Temp =95°C, Temperature Class T4 Process Temp =120°C as defined on nameplate. EU-type Cerificate No.: EMT17ATEX00021 X. ATEX Standards: EN IEC 60079-0, EN 60079-1, EN 60079-31.
IECEx Certified: For Ex db IIC T6 Gb, Ex ta IIIC T111°C Da, Process Temp =80°C, Temperature Class T5 Process Temp =95°C, Temperature Class T4 Process Temp =120°C as defined on nameplate.
IECEx Certificate of Conformity: Element IECEx EMT 17.0007X; IECEx Standards: IEC 60079-0, IEC 60079-1, IEC 60079-31.
UKCA Ex Certified for: UKCA 00518 Ex II 2 G Ex db IIC T6…T4 Gb / II 1 D Ex ta IIIC T111°C Da, T6 process temp ? 80°C, T5 process temp ? 95°C, T4 process temp ? 120°C. UKCA Ex Certificate of Conformity: EMA22UKEX00066X. UKCA Ex Standards: EN IEC 60079-0, EN 60079-1, EN 60079-31.
Weight:
2 lb 8 oz (1134 g).
Compliance:
ATEX, CE, FM, IECEx, UKCA Ex.
Note: References to ATEX apply to UKCA Ex.
Aplicaciones
–