PD2-7000 Helios Temperature Meter

Código: PD2-7000
Valorado con 0 de 5

Actualizado: 2024-02-21

Except where noted all specifications apply to operation at +25°C.GeneralDisplay: Two lines with 1.8\" (46 mm) high digits, red LEDs; 6 digits per line (-99999 to 999999), with lead zero blanking
Resolution: 1° or 0.1° for all thermocouples and RTD inputs
Display Intensity Eight user selectable intensity levels
Display Update Rate: 5/second (200 ms)
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Display Assignment: Line 1 and line 2 may be assigned to PV1, PV2, PCT, d r-u, d gross, d nt-g, max/min, max & min, set points, units (line 2 only), or Modbus input.
Programming Methods: Four programming buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
Noise Filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min Display: Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Password: Three programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only.
Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 10%. 12-24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental: Operating temperature range: -40 to 150°F (-40 to 65°C); Storage temperature range: -40 to 185°F (-40 to 85°C); Relative humidity: 0 to 90% non-condensing
Connections: Removable and integrated screw terminal blocks accept 12 to 22 AWG wire.
Enclosure: UL Type 4X, IP65 rated. Polycarbonate & glass blended plastic case, color: gray. Includes four PG11 through-hole conduit openings, with two factory installed PG11, IP68, black nylon threaded hole plugs with backing nuts.
Wall Mounting: Four (4) mounting holes provided for mounting meter to wall.
Pipe Mounting: Optional pipe mounting kit (PDA6260) allows for pipe mounting. Sold separately.
See PD2-7000 manual for instructions.
Tightening Torque: Removable Screw Terminals: 5 lb-in (0.56 Nm);
Digital I/O and RS485 Terminals: 2.2 lb-in (0.25 Nm)
Overall Dimensions: 10.63\" x 12.59\" x 4.77\" (270 mm x 319.7 mm x 121.2 mm) (H x W x D)
Weight: 6.10 lbs (2.76 kg)
UL File Number: UL & C-UL Listed. E160849; 508 Industrial Control Equipment.
Warranty: 3 years parts & labor
USB Connection: Compatibility: USB 2.0 Standard, Compliant
Connector Type: Micro-B receptacle
Cable: USB A Male to Micro-B Cable
Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
Power: USB PortTemperature InputInputs: Thermocouple: J, K, T, E, R, S, B, N, C; RTD: 100 ? platinum (0.00385 & 0.00392 coefficients), 10 ? copper, 120 ? nickel, 1000 ? platinum (0.00385 & 0.00392 coefficients)
Cold Junction Reference:Automatic, fixed, no user calibration needed
Temperature Drift: ±2°C maximum from 0 to 65°C ambient temperature ±4°C maximum from -20 to 0°C ambient temperature
Offset Adjustment: User programmable offset adjust ±50.0 degrees. This parameter allows the user to apply an offset value to the temperature being displayed.
Input Impedance:Greater than 100 k?
Sensor Break Detection: Open TC or RTD sensor indicated by display flashing oPEn, relays can be programmed to go \"On\", \"Off\", or to \"Ignore\" (Note: Ignore is detected as an upscale condition). Analog output goes to the programmed sensor break value.
RTD Averaging: Up to 10 RTDs connected in parallel can be averaged.
Accuracy & Ranges:TypeRange (°F)AccuracyRange (°C)AccuracyJ-200 to 2000±1.8°F-129 to 1093±1°CK-200 to 2400±1.8°F-129 to 1316±1°CT-200 to 752±1.8°F-129 to 400±1°CE-200 to 1800±1.8°F-129 to 982±1°CAR-50 to 3000±3.6°F-46 to 1649±2°CS-50 to 3000±3.6°F-46 to 1649±2°CB752 to 3300±3.6°F400 to 1816±2°CN-100 to 2300±3.6°F-73 to 1260±2°CC32 to 4100±3.6°F0 to 2260±2°C10?-328 to 500±0.2°F-200 to 260±0.1°C100?-328 to 1562±0.7°F-200 to 850±0.4°C120?-110 to 500±0.2°F-79 to 260±0.1°C1000?-328 to 900±0.7°F-200 to 482±0.4°CInput Impedance:Voltage Input: Greater than 3 M?, Current Input: 50 - 100 ?v
Input Overload: Voltage input protected up to 500 VDC. Current input protected up to 10 A by a 10A/300V fast acting non-resettable fuse. Fuse is NOT resettable after a fault; unit must be factory reconditioned.
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC, Logic Low: 0 to 1.25 VDC
RelaysRating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (? 50 W) @ 125/250 VAC for inductive loads
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads. See manual for details.
Deadband: 0-100% of span, user programmable
High Or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
Relay Operation: Automatic (non-latching) and/or manual reset; Latching (requires manual acknowledge) with/without clear; Pump alternation control (2 to 4 relays); Sampling (based on time); Off (disable unused relays and enable Interlock feature); Manual on/off control mode
Relay Reset: User selectable via front panel buttons or digital inputs
Automatic reset only (non-latching), when the input passes the reset point.Automatic + manual reset at any time (non-latching)Manual reset only, at any time (latching)Manual reset only after alarm condition has cleared (latching)
Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
Time Delay: 0 to 999.9 seconds, on & off relay time delays; Programmable and independent for each relay
Fail-Safe Operation: Programmable and independent for each relay. Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter OutputOutput Source: Process variable (PV), max, min, set points 1-4, Modbus input, or manual control mode
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Out Programming: 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
Accuracy: ± 0.1% of span ± 0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models rated @ 40 mA max.
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:
Power supplyMinimumMaximum24 VDC10 ?700 ?35 VDC (external)100 ?1200 ?
RS485 Serial Communications TerminalCompatibility: EIA-485
Connectors: Removable screw terminal connector
Max Distance: 3,937\' (1,200 m) max
Status Indication: Separate LEDs for Power (P), Transmit (TX), and Receive (RX)
Modbus® RTU Serial Communications ProtocolSlave: ID 1 – 247 (Meter address)
Baud Rate: 300 – 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte Timeout: 0.01 – 2.54 second
Turn Around Delay: Less than 2 ms (fixed)
Digital Input & Output TerminalChannels: 4 digital inputs & 4 digital outputs
Digital Input Logic High: 3 to 5 VDC
Digital Input Logic Low: 0 to 1.25 VDC
Digital Output Logic High: 3.1 to 3.3 VDC
Digital Output Logic Low: 0 to 0.4 VDC
Source Current: 10 mA maximum output current
Sink Current: 1.5 mA minimum input current
+5 V Terminal: To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4.WARNING! DO NOT use +5 V terminal to power external devices.

PD7000 ProVu Temperature Digital Panel Meter

Código: PD7000
Valorado con 0 de 5

Actualizado: 2024-02-21

GeneralDisplay: Upper display: 0.60\" (15 mm) high. Lower display: 0.46\" (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs.
Resolution: 1° (up to four digits) or 0.1° (up to five digits)
Display Intensity: Eight intensity levels
Display Update Rate: 5/second (200 ms)
Front Panel: NEMA 4X, IP65
Programming Methods:Four front panel buttons, digital inputs, PC and MeterView Pro software, Modbus registers.
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of span
Recalibration: Recommended at least every 12 months.
Max/Min Display: Max / min temperature readings are stored until reset by the user or until power to the meter is cycled.
Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
Power Options:85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only.
Normal Mode Rejection: Greater than 65 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output
Environmental:
Operating temperature range: -20 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black (92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
Dimensions: 4.68\" x 2.45\" x 5.64\" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment.
Warranty: 3 years parts & labor
USB Connection: Compatibility: USB 2.0 Standard, Compliant
   Connector Type: Micro-B receptacle
   Cable: USB A Male to Micro-B Cable
   Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit,
   Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
   Power: USB Port
Temperature InputInputs: Thermocouple J, K, T, E, R, S, B, N, C; RTD 100 ? platinum (0.00385 & 0.00392 curves), 10? copper, 120? nickel, 1000? platinum
Input Impedance: Greater than 100 k?
Offset Adjust: User programmable offset adjust ±50.0 degrees
Temperature Drift: ±2°C maximum from 0 to 65°C ambient temperature; ±4°C maximum from -20 to 0°C ambient temperature
Sensor Break: Display flashes \"Open\", relays can be programmed to go \"On\", \"Off\", or to \"Ignore\" (detected as an upscale condition).
Averaging: Up to 10 RTDs connected in parallel can be averaged.
Accuracy & Range:
Type     Range (°F)     Range (°C)AccuracyJ   -200 to 2000  -129 to 1093±1°CK   -200 to 2400  -129 to 1316±1°CT -200 to 752-129 to 400±1°CE   -200 to 1800-129 to 982±1°CR      -50 to 3000     -46 to 1649±2°CS      -50 to 3000     -46 to 1649±2°CB     752 to 3300    400 to 1816±2°CN   -100 to 2300     -73 to 1260±2°CC       32 to 4100         0 to 2260±2°C10 ? -328 to 500 -200 to 260±0.1°C100 ?   -328 to 1562 -200 to 850±0.4°C120 ? -110 to 500   -79 to 260±0.1°C1000 ? -328 to 900 -200 to 482±0.4°CRelaysRating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (? 50 watts) @ 125/250 VAC for inductive loads such as contactors, solenoids, etc.
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
Deadband: 0-100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), Off (disable unused relays and enable interlock feature, manual on/off control mode).
Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation: Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter OutputOutput Source: PV (temperature), max, min, set points 1-8, manual control setting, or Modbus input
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated 4-20 mA output
Accuracy: ±0.1% of span ± 0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models rated @ 40 mA max.
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:
Power supplyMinimumMaximum24 VDC10 ?700 ?35 VDC (external)100 ?1200 ?Serial CommunicationsProtocol: Modbus® RTU
Meter Address/Slave ID: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout: 0.01 - 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)
Note: Refer to the PD6000/PD7000 Modbus Register Tables for details, available in Documentation
Digital I/O Expansion ModuleChannels: 4 digital inputs & 4 digital outputs per module
System: Up to 2 modules for a total of 8 inputs & 8 outputs
Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
Digital Output Logic: High: 3.1 to 3.3 VDC Low: 0 to 0.4 VDC
Source Current: 10 mA maximum
Sink Current: 1.5 mA minimum
+5 V Terminal: To be used as pull-up for digital inputs only.
4-Relay Expansion ModuleRelays: Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (approx. 50 watts) @ 125/250 VAC for inductive loads.

PD743 Sabre T Low-Cost Temperature Digital Panel Meter

Código: PD743
Valorado con 0 de 5

Actualizado: 2024-02-21

GeneralDisplay: 0.56\" (14.2 mm) red LED, 4 digits (-1999 to 9999)
Front Panel: NEMA 4X, IP65; panel gasket provided
Programming Methods: Four front panel buttons
Display Update Rate: RTD: 5/sec; TC: 2.5/sec
Overrange: Display flashes 9999
Underrange: Display flashes -1999
Recalibration: All inputs are calibrated at the factory; recalibration is recommended at least every 12 months
Max/Min Display: Stored until reset by user or meter is turned off
Password: Restricts modification of programmed settings
Non-Volatile Memory: Settings stored for a minimum of 10 years
Power Options: 85-265 VAC, 50/60 Hz; 90-265 VDC, 8 W max or 12-36 VDC; 12-24 VAC, 6 W max
Required Fuse: UL Recognized, 5 A max, slow-blow; up to 6 meters may share one fuse
Normal Mode Rejection: 64 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line
Operating Temperature: 0 to 65°C
Storage Temperature: -40 to 85°C
Relative Humidity: 0 to 90%
Connections: Power & Signal: removable screw terminal blocks accept 12 to 22 AWG. Note: RJ11 header for factory use only
Enclosure: 1/8 DIN, high impact plastic, 94 V-0, color; gray
Weight: 8.5 oz (241 g)
UL File Number: E160849; 508 Industrial Control Equipment
Warranty: 1 year parts & labor Temperature InputsInputs: Factory calibrated, field selectable: type J, K, T, or E thermocouples and 100 ? platinum RTD (0.00385 or 0.00392 curve)
Resolution: 1°; type T: 1° or 0.1°
Cold Junction Reference: Automatic
Temperature Drift: ±2°C maximum
Input Impedance: Greater than 100 k ?TypeRangeAccuracyRangeAccuracyJ-58º to 1382ºF±2ºF-50º to 750ºC±1ºCK-58º to 2300ºF±2ºF-50º to 1260ºC±1ºCT-292º to 700ºF±2ºF-180º to 371ºC±1ºCE-58º to 1700ºF±2ºF-50º to 927ºC±1ºCRTD-328º to 1382ºF±1ºF-200º to 750ºC±1ºC